Thane(W), Maharashtra, India – 400604 9.00 am - 6.00 pm
vintexfire@gmail.com +91 8691070213

Spray Nozzle

Revolving Nozzle
Fire Extinguisher Image

Technical Specification

• Hub Sides & Wall Bracket -M.S. Sheet of IS:513
• Swivel Joint -LTB-2 of IS:318
• Pipe with Fitting -Steel of IS:1239 Part I
• Branch Pipe with Nozzle -IS:8090
• Hose Reel Tubing -Hydraulic Rubber Hose Conf to IS:444

Water Curtain Nozzle
Fire Extinguisher Image

Technical Specification

• Model: WC - Brass construction
• Model: WCS - Stainless Steel construction
• Size : 1/2" & 3/4" BSPT
• Non-automatic open orifice, fix pattern used as curtain nozzle or as window nozzle

Tank Cooling Nozzle
Fire Extinguisher Image

Technical Specification

• Model: TC15 - Brass construction
• Model: TC15S - Stainless Steel construction
• Size : 1/2" & 3/4" BSPT
• Non-automatic open orifice, fix pattern used as curtain nozzle

Jumbo Water Curtain Nozzle
Fire Extinguisher Image

Technical Specification

• Model: JC - Bronze construction and Model: JCS Stainless Steel construction
• Used to segregate the area by creating water curtain
• Size: 65, 80 or 100 mm flanged end (2.5", 3" or 4")
• Flow at 6.9 bar (100 psi), 1000 to 3000 lpm (264 to 792 gpm)
• Produces flat water curtain projecting upwards

Reverse Action Water Spray Nozzle
Fire Extinguisher Image

Technical Specification

• Size 1/2" BSPT / NPT
• Open orifice used in deluge water spray system
• Non-automatic fixed pattern external deflector
• Solid cone discharge in the opposite direction of water inlet
• Combination of different orifices & spray angle
• K-Factor : Metric - 22, 30, 35, 41, 51, 64, 91 & 102
• K-Factor : US - 1.54, 2.10, 2.45, 2.87, 3.57, 4.48, 5.53, 6.63 & 7.14
• Spray angle - 120° & 140°
• Brass finish or Chrome plated
• Nozzles are permanently marked with Model No., Batch No., Spray Angle & K-Factor

High Velocity Spray Nozzle HV – AS & BS
Fire Extinguisher Image

Technical Specification

• Non-automatic, open orifice, directional spray nozzle
• Model - HV-AS in Brass material with Copper strainer
• For high velocity water application for protection of flammable liquid and electric transformers
• K-factor: K-22 x 75°, K-18 x 80°, K-26 x 100°, K-32 x 90°, K-42 x 115° and K-23 x 120°
• ¾” BSPT/NPT connection
• Nozzle also available with blow-off cap
• UL Listed

Medium Velocity Spray Nozzles
Fire Extinguisher Image

Technical Specification

• Brass construction for Model MV-A and MV-AS
• Stainless Steel construction for Model MV-B and MV-BS
• Aluminium Bronze construction for Model MV-E
• Size 1/2" BSPT or NPT
• Open orifice design used in deluge water spray system
• Non-automatic fixed pattern, external deflector
• Solid cone discharge
• Several combination of different orifice sizes & spray angles
• K-factor(Metric) - 18, 22, 30, 35, 41, 51, 64, 79, 91 & 102
• K-factor(US) - 1.26, 1.54, 2.10, 2.45, 2.87, 3.57, 4.48, 5.53, 6.37 & 7.14
• Spray angle - 65°, 80°, 90°, 100°, 110°, 120° & 140°
• Each Nozzle body permanently marked with model number, batch number, spray angle, K-factor & UL mark
• Finish - Brass, Bright Nickel Chrome or Natural Finish
• Approvals - UL Listed and FM Approved
• FM Approved Blow-Off Plug